The Fluke 1555 insulation resistance tester kit offers digital insulation testing up to 10 kV in an industrial strength case, with all the heavy duty leads and clips you need. Plus, the Fluke Connect wireless app performs tests and collects data while you stay a safe distance away.
Remote operation lets you spend as little time as possible in potentially hazardous zones. Real-time trending shows a live graph on your phone, rather than a hard-to-read set of changing values. And you can create reports quickly, using pre-designed templates that you can customize with company logos.
Fluke insulation testers can now conduct the entire range of test voltages specified in IEEE 43-2000 with a best in class, 3 year warranty and CAT IV 600 V safety rating.
Other useful features:
Electrical Specifications | ||
The tester's accuracy is specified for one year after calibration at operating temperatures of 0°C to 35°C. For operating temperatures outside the range (-20°C to 0°C and 35°C to 50°C), add ±.25% per °C, except on the 20% bands add ±1% per °C. | ||
Insulation Resistance Measurement | ||
Test voltage (DC) | ||
250 V | Range | < 250 kΩ, 250 kΩ to 5 GΩ 5 GΩ to 50 GΩ > 50 GΩ |
Accuracy (± reading) | Unspecified 5% 20% Unspecified |
|
500 V | Range | < 500 kΩ 500 kΩ to 10 GΩ 10 GΩ to 100 GΩ > 100 GΩ |
Accuracy (± reading) | Unspecified 5% 20% Unspecified |
|
1000 V | Range | < 1 MΩ 1 MΩ to 20 GΩ 20 GΩ to 200 GΩ > 200 GΩ |
Accuracy (± reading) | Unspecified 5% 20% Unspecified |
|
2500 V | Range | < 2.5 MΩ 2.5 MΩ to 50 GΩ 50 GΩ to 500 GΩ > 500 GΩ |
Accuracy (± reading) | Unspecified 5% 20% Unspecified |
|
5000 V | Range | < 5 MΩ 5 MΩ to 100 GΩ 100 GΩ to 1 TΩ > 1 TΩ |
Accuracy (± reading) | Unspecified 5% 20% Unspecified |
|
10000 V | Range | < 10 MΩ 10 MΩ to 200 GΩ 200 GΩ to 2 TΩ > 2 TΩ |
Accuracy (± reading) | Unspecified 5% 20% Unspecified |
|
Bar graph range | 0 to 1 TΩ (1550C) - 0 to 2 TΩ (1555) | |
Insulation test voltage accuracy | -0%, +10% at 1 mA load current | |
Induced AC mains current rejection | 2 mA maximum | |
Charging rate for capacitive load | 5 seconds per μF | |
Discharge rate for capacitive load | 1.5 s/μF | |
Leakage current measurement | Range | 1 nA to 2 mA |
Accuracy | ±(5% + 2 nA) | |
Capacitance measurement | Range | 0.01 μF to 15.00 μF |
Accuracy | ±(15% rdg + 0.03 μF) | |
Timer | Range | 0 to 99 minutes |
Resolution setting | 1 minute | |
Resolution indication | 1 second | |
Live circuit warning | Warning range | 30 V to 660 V AC/DC, 50/60 Hz |
Voltage accuracy | ±(15% + 2 V) | |
Software specifications | FlukeView Forms™ basic software requires a PC running Windows XP, Windows Vista , Windows 7 or Windows 8. | |
General Specifications | ||
Display | 75 x 105 mm | |
Power | 12 V lead-acid rechargeable battery, Yuasa NP2.8-12 | |
Charger Input (AC) | 85 V to 250 V AC 50/60 Hz 20 VA | |
This Class II (double insulated) instrument is supplied with a Class 1 (grounded) power cord. The protective earth terminal (ground pin) is not connected internally. The extra pin is for added plug retention only. | ||
Dimensions | 269 x 277 x 160 mm (10.6 x 10.9 x 6.3 in) | |
Weight | 3.7 kg (8.2 lb) | |
Temperature (operating) | -20°C to 50°C (-4°F to 122°F) | |
Temperature (storage) | -20°C to 65°C (-4°F to 149°F) | |
Humidity | 80% to 31°C decreasing linearly to 50% at 50°C | |
Altitude | 2000 m | |
Enclosure sealing | IP40 | |
Input overload protection | 1000 V AC | |
Electromagnetic compatibility | EN 61326 | |
Safety compliance | IEC 61010-1: Overvoltage category II, Pollution Degree 2. IEC 61010-2-030: Measurement 600V CAT IV / 1000V CAT III IEC 61557-1, IEC 61557-2 |